UTB Envirotec 30-year anniversary logo

Contact

← All case studies

Tiszatelek

Tiszatelek, Hungary

CYCLATORMunicipal
Decanter installed in a circular CYCLATOR tank at the Tiszatelek municipal wastewater treatment plant, Hungary

Scope of supply

UTB delivered the septic waste treatment plant at Tiszatelek built on ICEAS, completed 2006.

  • 200 m³/day
  • 2,667 PE
  • ICEAS
  • Septic waste treatment plant
  • Completed 2006.
LocationTiszatelek, Hungary
SegmentMunicipal
Capacity200 m³/day
TechnologiesCYCLATOR

Parameters as commissioned

Influent, the consent limit, and the effluent quality actually measured.

Parameter Influent (mg/l) Effluent Limit (mg/l) Effluent Quality (mg/l)
CODKr 1,600 125 48
BOD5 800 25 15
TN 188 55 49
NH4-N 150 20 1
TSS 800 35 28
TP 25 10 9.6

On site

Decanter installed in a circular CYCLATOR tank at the Tiszatelek municipal wastewater treatment plant, HungaryWalkway and pipework over the circular CYCLATOR tank at Tiszatelek, HungaryDecanter arm on the wall of the CYCLATOR tank at Tiszatelek, Hungary